Hazet 2019 Tool Catalogue
2 kg 120 mm 252 Valid until December 31, 2019 Components and spare parts from page 474 to 482 Hand tools VDE Tools for Electricians Requirements for a VDE protective insulation using the example of a HAZET VDE torque wrench Electrical test [type testing] No breakdowns or arcing may occur in the vicinity of the insulation after 48 hours of moisture-proof storage with a 3-minute measurement under 10,000 V. Cold impact test [type testing]: With a retention time of 2 hours at an ambient temperature of -25 °C, the insulation must not present any cracks or other damage during targeted shocks and impacts (falling height 0.6 m). Burn test [type testing]: After 10 seconds in a flame, the insulation must not prove to be “easily combustible”. Pressure test [type testing]: After being stored for 2 hours at a temperature of 70 °C, with a pressure load of 20 N and a 3-minute measurement under 5,000 V, there must be no punctures or arcing in the insulation. Test for adhesion: The insulation must not come loose or slacken when under a tensile load for 3 minutes with 500 N after 168 hours in a climatic chamber at +70°C. All VDE tools go through a 10,000 V individual inspection! 20 sec. 5000 V 2 kg = ^ 20N 3 min. 3 min. 50 kg +70 °C 10 sec. at 2 m + 23 °C at 0.6 m – 25 °C